LV power cables

SWA Armoured Cable BS 5467, 600/1000 V

Steel wire armour for direct burial, outdoor and industrial runs.

Cross-section
1.5 – 400 mm²
Rated voltage
0.6/1 kV
Standard
BS 5467

XLPE-insulated copper power cable to BS 5467 with galvanised steel wire armour (aluminium wire for single-core) and black PVC sheath. The armour gives mechanical protection and serves as circuit protective conductor; LSZH-sheathed versions to BS 6724 are available.

ModelsBS 5467 4C×35 SWACU/XLPE/SWA/PVCYJV32 / YJV22

  • BS 5467
  • IEC 60502-1
  • IEC 60332-1-2

Highlights

  • 2 – 5 cores, 1.5 – 400 mm²
  • Galvanised steel wire armour
  • Armour usable as CPC
  • BS 6724 LSZH version

Technical data

ModelBS 5467 4C×35 SWACU/XLPE/SWA/PVCYJV32 / YJV22
Rated voltage600/1000 V
ConductorPlain copper, class 2; circular or sector-shaped
Cross-section2 – 5 cores, 1.5 – 400 mm²
InsulationXLPE (GP8)
ArmourGalvanised steel wire (SWA) for multi-core; aluminium wire (AWA) for single-core
Outer sheathPVC (ST2), black; LSZH to BS 6724 on request
Operating temperature90 °C continuous conductor temperature
Short-circuit temperature250 °C, 5 s
Flame retardancyFlame retardant, IEC 60332-1-2
Min. bending radius6 × D (circular) · 8 × D (sector)
ApplicationDirect burial, ducts, cable trays and outdoor runs where mechanical protection is needed
PackagingDrums of 250 / 500 / 1,000 m
StandardBS 5467, IEC 60502-1

BS 5467 four-core SWA — construction & ratings

Cross-sectionmm²Armour wire diametermmOuter diameter≈mmApprox. weight≈kg/kmMax. DC resistance20 °CΩ/kmCurrent rating, clipped directA
4 × 1.50.9014.042012.125
4 × 2.50.9015.55307.4133
4 × 40.9017.57204.6143
4 × 61.2519.08803.0856
4 × 101.2521.51,2001.8378
4 × 161.2524.01,6001.1599
4 × 251.6028.02,3000.727131
4 × 351.6030.02,8000.524162
4 × 501.6032.03,4000.387197
4 × 702.0036.04,5000.268251
4 × 952.0041.05,9000.193304
4 × 1202.0045.07,2000.153353
4 × 1502.0050.08,8000.124406
4 × 1852.5055.010,6000.0991463
4 × 2402.5061.013,5000.0754546
4 × 3002.5066.016,4000.0601628

Standard reference values: current ratings per BS 7671 table 4E4A (clipped direct, 30 °C, three-phase); dimensions and weights are typical. Non-standard designs on request.

Inquire about this cable

SWA Armoured Cable BS 5467, 600/1000 V

Typical reply within one working day.

or sales@xinyapower.com