Cable size calculator (IEC 60364-5-52)

Enter load, voltage, length and installation method. The calculator checks current-carrying capacity and voltage drop and picks the standard cross-section — then our engineers confirm it.

Supply
Installation
Conductor

Recommended size

—mm²

Design current
—
Rated capacity
—
Voltage drop
—

Suggested cables

    Send this result for a quote

    Indicative: XLPE multicore cable to IEC 60364-5-52, single circuit, no grouping factor. Final sizing (grouping, short-circuit, protection) is confirmed by our engineers.

    How the calculation works

    1. 01

      Design current: I = P ÷ (√3 · U · cos φ) for three-phase, I = P ÷ (U · cos φ) for single-phase.

    2. 02

      Current-carrying capacity: IEC 60364-5-52 reference values for XLPE-insulated multicore cable (method E in air, B2 in conduit, D1 in buried ducts), corrected for ambient temperature.

    3. 03

      Voltage drop: ΔU = √3 · I · L · (R cos φ + X sin φ), with conductor resistance at 90 °C and X ≈ 0.08 Ω/km.

    4. 04

      The smallest standard size that passes both checks is selected; above 300 mm² the calculator splits the circuit into parallel runs.