Calculator
Cable size calculator (IEC 60364-5-52)
Enter load, voltage, length and installation method. The calculator checks current-carrying capacity and voltage drop and picks the standard cross-section — then our engineers confirm it.
Recommended size
—mm²
- Design current
- —
- Rated capacity
- —
- Voltage drop
- —
Suggested cables
Indicative: XLPE multicore cable to IEC 60364-5-52, single circuit, no grouping factor. Final sizing (grouping, short-circuit, protection) is confirmed by our engineers.
How the calculation works
- 01
Design current: I = P ÷ (√3 · U · cos φ) for three-phase, I = P ÷ (U · cos φ) for single-phase.
- 02
Current-carrying capacity: IEC 60364-5-52 reference values for XLPE-insulated multicore cable (method E in air, B2 in conduit, D1 in buried ducts), corrected for ambient temperature.
- 03
Voltage drop: ΔU = √3 · I · L · (R cos φ + X sin φ), with conductor resistance at 90 °C and X ≈ 0.08 Ω/km.
- 04
The smallest standard size that passes both checks is selected; above 300 mm² the calculator splits the circuit into parallel runs.
Most requested cables
Made in our plant
LV power cables0.6/1 kV XLPE Copper Power Cable (CU/XLPE/PVC)
CU/XLPE/PVC 4×95
- Cross-section
- 1.5 – 630 mm²
- Rated voltage
- 0.6/1 kV
- Standard
- IEC 60502-1
Made in our plant
LV power cablesSWA Armoured Cable BS 5467, 600/1000 V
BS 5467 4C×35 SWA
- Cross-section
- 1.5 – 400 mm²
- Rated voltage
- 0.6/1 kV
- Standard
- BS 5467
LV power cables0.6/1 kV Aluminium XLPE Power Cable
NA2XY 4×150
- Cross-section
- 16 – 630 mm²
- Rated voltage
- 0.6/1 kV
- Standard
- IEC 60502-1
Fire-resistant & LSZH cablesFire-Resistant Cable 0.6/1 kV (IEC 60331, BS 6387 CWZ)
NHXH FE180 E90
- Cross-section
- 1.5 – 400 mm²
- Rated voltage
- 0.6/1 kV
- Standard
- IEC 60331
Send us your cable schedule.
Types, sizes, lengths and destination are enough. An engineer replies with a checked selection, drum plan and quotation within one working day.