Single-Core MV XLPE Cable 6/10 – 26/35 kV (Cu / Al)
Triple-extruded on our own CCV line — the backbone of substations, wind farms and city networks.
- Cross-section
- 35 – 630 mm²
- Rated voltage
- 3.6/6 – 26/35 kV
- Standard
- IEC 60502-2
Single-core medium-voltage cable to IEC 60502-2 with compacted copper or aluminium conductor, conductor screen, XLPE insulation and insulation screen extruded in one pass, copper wire screen sized to your fault level and a PVC or PE sheath. Every length passes partial-discharge and AC voltage tests before it leaves the factory.
ModelsN2XSY 1×240/25 18/30 kVNA2XS(F)2Y 1×400/35YJV 26/35 kV 1×50 – 1×630
- IEC 60502-2
- IEC 60228
- IEC 60332-1-2
- GB/T 12706.2
Highlights
- 3.6/6 to 26/35 kV, 35 – 630 mm²
- Triple extrusion, dry-cured on a CCV line
- Copper wire screen 16 – 35 mm² to fault level
- Watertight and termite-proof options
Technical data
| Model | N2XSY 1×240/25 18/30 kV | NA2XS(F)2Y 1×400/35 | YJV 26/35 kV 1×50 – 1×630 |
|---|---|---|---|
| Rated voltage | 3.6/6, 6/10, 8.7/15, 12/20, 18/30, 26/35 kV | ||
| Conductor | Compacted copper or aluminium, class 2 (IEC 60228); longitudinally watertight on request | ||
| Cross-section | 1 × 35 – 1 × 630 mm² (800 mm² on request) | ||
| Construction | Conductor screen, XLPE insulation and insulation screen extruded in one pass (triple extrusion, CCV line) | ||
| Insulation | XLPE, 8.0 mm nominal at 18/30 kV | ||
| Metallic screen | Copper wire screen with counter-helix copper tape, 16 – 35 mm² (to fault level) | ||
| Outer sheath | PVC (ST2) or MDPE / HDPE (ST7); red or black | ||
| Operating temperature | 90 °C continuous conductor temperature | ||
| Short-circuit temperature | 250 °C, 5 s | ||
| Flame retardancy | Flame retardant, IEC 60332-1-2 | ||
| Partial discharge | ≤ 5 pC at 1.73 U₀ (routine test on every length) | ||
| Min. bending radius | 15 × D during installation · 10 × D at terminations | ||
| Packaging | Steel or wooden drums, 500 – 1,000 m per drum, ends sealed with caps | ||
| Standard | IEC 60502-2, GB/T 12706.2 | ||
18/30 kV single-core copper — construction & ratings
| Cross-sectionmm² | Outer diameter≈mm | Approx. weight≈kg/km | Max. DC resistance20 °CΩ/km | Current rating, in groundA | Current rating, in airA |
|---|---|---|---|---|---|
| 1 × 50 | 31 | 1,250 | 0.387 | 195 | 235 |
| 1 × 70 | 33 | 1,500 | 0.268 | 240 | 290 |
| 1 × 95 | 35 | 1,800 | 0.193 | 285 | 350 |
| 1 × 120 | 36 | 2,100 | 0.153 | 320 | 400 |
| 1 × 150 | 38 | 2,400 | 0.124 | 355 | 450 |
| 1 × 185 | 40 | 2,800 | 0.0991 | 400 | 515 |
| 1 × 240 | 43 | 3,500 | 0.0754 | 465 | 610 |
| 1 × 300 | 45 | 4,200 | 0.0601 | 520 | 700 |
| 1 × 400 | 49 | 5,200 | 0.047 | 590 | 805 |
| 1 × 500 | 52 | 6,400 | 0.0366 | 665 | 920 |
| 1 × 630 | 56 | 7,900 | 0.0283 | 745 | 1050 |
Standard reference values: current ratings for one circuit in trefoil, 90 °C conductor, 20 °C soil (1.5 K·m/W) or 30 °C air; dimensions and weights are typical. Final data depend on screen size and sheath — non-standard designs on request.
Related products
Made in our plant
MV & HV power cablesThree-Core MV XLPE Armoured Cable 8.7/15 kV
N2XSEYBY 3×95 8.7/15 kV
- Cross-section
- 3 × 35 – 3 × 300 mm²
- Rated voltage
- 3.6/6 – 18/30 kV
- Standard
- IEC 60502-2
MV & HV power cablesHV XLPE Cable 64/110 kV, Corrugated Aluminium Sheath
2XS(FL)2Y 1×800 64/110 kV
- Cross-section
- 240 – 1,600 mm²
- Rated voltage
- 38/66 – 76/132 kV
- Standard
- IEC 60840
Made in our plant
LV power cables0.6/1 kV XLPE Copper Power Cable (CU/XLPE/PVC)
CU/XLPE/PVC 4×95
- Cross-section
- 1.5 – 630 mm²
- Rated voltage
- 0.6/1 kV
- Standard
- IEC 60502-1
Inquire about this cable
Single-Core MV XLPE Cable 6/10 – 26/35 kV (Cu / Al)
Typical reply within one working day.