MV & HV power cables

Single-Core MV XLPE Cable 6/10 – 26/35 kV (Cu / Al)

Triple-extruded on our own CCV line — the backbone of substations, wind farms and city networks.

Cross-section
35 – 630 mm²
Rated voltage
3.6/6 – 26/35 kV
Standard
IEC 60502-2

Single-core medium-voltage cable to IEC 60502-2 with compacted copper or aluminium conductor, conductor screen, XLPE insulation and insulation screen extruded in one pass, copper wire screen sized to your fault level and a PVC or PE sheath. Every length passes partial-discharge and AC voltage tests before it leaves the factory.

ModelsN2XSY 1×240/25 18/30 kVNA2XS(F)2Y 1×400/35YJV 26/35 kV 1×50 – 1×630

  • IEC 60502-2
  • IEC 60228
  • IEC 60332-1-2
  • GB/T 12706.2

Highlights

  • 3.6/6 to 26/35 kV, 35 – 630 mm²
  • Triple extrusion, dry-cured on a CCV line
  • Copper wire screen 16 – 35 mm² to fault level
  • Watertight and termite-proof options

Technical data

ModelN2XSY 1×240/25 18/30 kVNA2XS(F)2Y 1×400/35YJV 26/35 kV 1×50 – 1×630
Rated voltage3.6/6, 6/10, 8.7/15, 12/20, 18/30, 26/35 kV
ConductorCompacted copper or aluminium, class 2 (IEC 60228); longitudinally watertight on request
Cross-section1 × 35 – 1 × 630 mm² (800 mm² on request)
ConstructionConductor screen, XLPE insulation and insulation screen extruded in one pass (triple extrusion, CCV line)
InsulationXLPE, 8.0 mm nominal at 18/30 kV
Metallic screenCopper wire screen with counter-helix copper tape, 16 – 35 mm² (to fault level)
Outer sheathPVC (ST2) or MDPE / HDPE (ST7); red or black
Operating temperature90 °C continuous conductor temperature
Short-circuit temperature250 °C, 5 s
Flame retardancyFlame retardant, IEC 60332-1-2
Partial discharge≤ 5 pC at 1.73 U₀ (routine test on every length)
Min. bending radius15 × D during installation · 10 × D at terminations
PackagingSteel or wooden drums, 500 – 1,000 m per drum, ends sealed with caps
StandardIEC 60502-2, GB/T 12706.2

18/30 kV single-core copper — construction & ratings

Cross-sectionmm²Outer diameter≈mmApprox. weight≈kg/kmMax. DC resistance20 °CΩ/kmCurrent rating, in groundACurrent rating, in airA
1 × 50311,2500.387195235
1 × 70331,5000.268240290
1 × 95351,8000.193285350
1 × 120362,1000.153320400
1 × 150382,4000.124355450
1 × 185402,8000.0991400515
1 × 240433,5000.0754465610
1 × 300454,2000.0601520700
1 × 400495,2000.047590805
1 × 500526,4000.0366665920
1 × 630567,9000.02837451050

Standard reference values: current ratings for one circuit in trefoil, 90 °C conductor, 20 °C soil (1.5 K·m/W) or 30 °C air; dimensions and weights are typical. Final data depend on screen size and sheath — non-standard designs on request.

Inquire about this cable

Single-Core MV XLPE Cable 6/10 – 26/35 kV (Cu / Al)

Typical reply within one working day.

or sales@xinyapower.com