LV power cables
0.6/1 kV XLPE Copper Power Cable (CU/XLPE/PVC)
The everyday power cable for switchboards, feeders and sub-mains.
- Cross-section
- 1.5 – 630 mm²
- Rated voltage
- 0.6/1 kV
- Standard
- IEC 60502-1
Low-voltage power cable to IEC 60502-1 with plain copper conductors, XLPE insulation rated 90 °C and a black PVC sheath. One to five cores, circular or sector-shaped, with reduced neutral sizes on request — the standard choice for building and industrial distribution.
ModelsCU/XLPE/PVC 4×95N2XY 4×16YJV 0.6/1 kV 1 – 5 cores
- IEC 60502-1
- IEC 60228
- IEC 60332-1-2
- GB/T 12706.1
Highlights
- 1 – 5 cores, 1.5 – 630 mm²
- XLPE 90 °C: about 20 % more current than PVC
- IEC colour code or customer colours
- Drums of 250 – 1,000 m
Technical data
| Model | CU/XLPE/PVC 4×95 | N2XY 4×16 | YJV 0.6/1 kV 1 – 5 cores |
|---|---|---|---|
| Rated voltage | 0.6/1 kV (Um 1.2 kV) | ||
| Test voltage | 3.5 kV AC, 5 min | ||
| Conductor | Plain annealed copper, class 1 / class 2; circular or sector-shaped | ||
| Cross-section | 1 – 5 cores, 1.5 – 630 mm² (reduced neutral, e.g. 3 × 185 + 95) | ||
| Insulation | XLPE | ||
| Colour | Cores: brown, black, grey, blue, green-yellow (IEC 60446) or to order | ||
| Outer sheath | PVC (ST2), black; UV resistant | ||
| Operating temperature | 90 °C continuous conductor temperature | ||
| Short-circuit temperature | 250 °C, 5 s | ||
| Flame retardancy | Flame retardant, IEC 60332-1-2 | ||
| Min. bending radius | 12 × D (multi-core) · 15 × D (single-core) | ||
| Packaging | Drums of 250 – 1,000 m; coils of 100 m for small sizes | ||
| Standard | IEC 60502-1, GB/T 12706.1 | ||
0.6/1 kV four-core copper XLPE — construction & ratings
| Cross-sectionmm² | Outer diameter≈mm | Approx. weight≈kg/km | Max. DC resistance20 °CΩ/km | Current rating, in airA | Current rating, in groundA |
|---|---|---|---|---|---|
| 4 × 1.5 | 10.5 | 170 | 12.1 | 23 | 19 |
| 4 × 2.5 | 11.5 | 230 | 7.41 | 32 | 24 |
| 4 × 4 | 13.0 | 320 | 4.61 | 42 | 31 |
| 4 × 6 | 14.0 | 420 | 3.08 | 54 | 39 |
| 4 × 10 | 16.5 | 640 | 1.83 | 75 | 52 |
| 4 × 16 | 19.0 | 930 | 1.15 | 100 | 67 |
| 4 × 25 | 23.0 | 1,400 | 0.727 | 127 | 86 |
| 4 × 35 | 25.0 | 1,850 | 0.524 | 158 | 103 |
| 4 × 50 | 29.0 | 2,400 | 0.387 | 192 | 122 |
| 4 × 70 | 33.0 | 3,300 | 0.268 | 246 | 151 |
| 4 × 95 | 37.0 | 4,400 | 0.193 | 298 | 179 |
| 4 × 120 | 41.0 | 5,500 | 0.153 | 346 | 203 |
| 4 × 150 | 45.0 | 6,800 | 0.124 | 399 | 230 |
| 4 × 185 | 50.0 | 8,400 | 0.0991 | 456 | 258 |
| 4 × 240 | 56.0 | 10,900 | 0.0754 | 538 | 297 |
| 4 × 300 | 62.0 | 13,500 | 0.0601 | 621 | 336 |
Standard reference values: current ratings per IEC 60364-5-52 (single circuit, 30 °C air / 20 °C soil, no grouping); dimensions and weights are typical. Non-standard designs on request.
Related products
Made in our plant
LV power cablesSWA Armoured Cable BS 5467, 600/1000 V
BS 5467 4C×35 SWA
- Cross-section
- 1.5 – 400 mm²
- Rated voltage
- 0.6/1 kV
- Standard
- BS 5467
LV power cables0.6/1 kV Aluminium XLPE Power Cable
NA2XY 4×150
- Cross-section
- 16 – 630 mm²
- Rated voltage
- 0.6/1 kV
- Standard
- IEC 60502-1
Made in our plant
MV & HV power cablesSingle-Core MV XLPE Cable 6/10 – 26/35 kV (Cu / Al)
N2XSY 1×240/25 18/30 kV
- Cross-section
- 35 – 630 mm²
- Rated voltage
- 3.6/6 – 26/35 kV
- Standard
- IEC 60502-2
Inquire about this cable
0.6/1 kV XLPE Copper Power Cable (CU/XLPE/PVC)