LV power cables

0.6/1 kV XLPE Copper Power Cable (CU/XLPE/PVC)

The everyday power cable for switchboards, feeders and sub-mains.

Cross-section
1.5 – 630 mm²
Rated voltage
0.6/1 kV
Standard
IEC 60502-1

Low-voltage power cable to IEC 60502-1 with plain copper conductors, XLPE insulation rated 90 °C and a black PVC sheath. One to five cores, circular or sector-shaped, with reduced neutral sizes on request — the standard choice for building and industrial distribution.

ModelsCU/XLPE/PVC 4×95N2XY 4×16YJV 0.6/1 kV 1 – 5 cores

  • IEC 60502-1
  • IEC 60228
  • IEC 60332-1-2
  • GB/T 12706.1

Highlights

  • 1 – 5 cores, 1.5 – 630 mm²
  • XLPE 90 °C: about 20 % more current than PVC
  • IEC colour code or customer colours
  • Drums of 250 – 1,000 m

Technical data

ModelCU/XLPE/PVC 4×95N2XY 4×16YJV 0.6/1 kV 1 – 5 cores
Rated voltage0.6/1 kV (Um 1.2 kV)
Test voltage3.5 kV AC, 5 min
ConductorPlain annealed copper, class 1 / class 2; circular or sector-shaped
Cross-section1 – 5 cores, 1.5 – 630 mm² (reduced neutral, e.g. 3 × 185 + 95)
InsulationXLPE
ColourCores: brown, black, grey, blue, green-yellow (IEC 60446) or to order
Outer sheathPVC (ST2), black; UV resistant
Operating temperature90 °C continuous conductor temperature
Short-circuit temperature250 °C, 5 s
Flame retardancyFlame retardant, IEC 60332-1-2
Min. bending radius12 × D (multi-core) · 15 × D (single-core)
PackagingDrums of 250 – 1,000 m; coils of 100 m for small sizes
StandardIEC 60502-1, GB/T 12706.1

0.6/1 kV four-core copper XLPE — construction & ratings

Cross-sectionmm²Outer diameter≈mmApprox. weight≈kg/kmMax. DC resistance20 °CΩ/kmCurrent rating, in airACurrent rating, in groundA
4 × 1.510.517012.12319
4 × 2.511.52307.413224
4 × 413.03204.614231
4 × 614.04203.085439
4 × 1016.56401.837552
4 × 1619.09301.1510067
4 × 2523.01,4000.72712786
4 × 3525.01,8500.524158103
4 × 5029.02,4000.387192122
4 × 7033.03,3000.268246151
4 × 9537.04,4000.193298179
4 × 12041.05,5000.153346203
4 × 15045.06,8000.124399230
4 × 18550.08,4000.0991456258
4 × 24056.010,9000.0754538297
4 × 30062.013,5000.0601621336

Standard reference values: current ratings per IEC 60364-5-52 (single circuit, 30 °C air / 20 °C soil, no grouping); dimensions and weights are typical. Non-standard designs on request.

Inquire about this cable

0.6/1 kV XLPE Copper Power Cable (CU/XLPE/PVC)

Typical reply within one working day.

or sales@xinyapower.com