MV & HV power cables

Three-Core MV XLPE Armoured Cable 8.7/15 kV

Three screened cores, one armoured cable — buried feeders without extra protection.

Cross-section
3 × 35 – 3 × 300 mm²
Rated voltage
3.6/6 – 18/30 kV
Standard
IEC 60502-2

Three-core medium-voltage cable to IEC 60502-2: each XLPE core individually screened with copper tape, laid up with fillers and protected by steel tape or steel wire armour under a PVC sheath. Laid directly in the ground for distribution feeders, industrial ring mains and transformer connections.

ModelsN2XSEYBY 3×95 8.7/15 kVYJV22 3×240 8.7/15 kVXY-MV3-SWA

  • IEC 60502-2
  • IEC 60228
  • GB/T 12706.3

Highlights

  • 3 × 35 – 3 × 300 mm², up to 18/30 kV
  • Copper tape screen on every core
  • STA or SWA armour for direct burial
  • Copper or aluminium conductors

Technical data

ModelN2XSEYBY 3×95 8.7/15 kVYJV22 3×240 8.7/15 kVXY-MV3-SWA
Rated voltage3.6/6, 6/10, 8.7/15, 12/20, 18/30 kV
ConductorCompacted copper or aluminium, class 2
Cross-section3 × 35 – 3 × 300 mm²
ConstructionThree screened XLPE cores laid up with fillers, bedding, armour, outer sheath
InsulationXLPE, triple extruded; 4.5 mm nominal at 8.7/15 kV
Metallic screenCopper tape on each core
ArmourDouble galvanised steel tape (STA) or galvanised steel wire (SWA)
Outer sheathPVC (ST2), black; LSZH or HDPE on request
Operating temperature90 °C continuous conductor temperature
Short-circuit temperature250 °C, 5 s
Flame retardancyFlame retardant, IEC 60332-1-2
Min. bending radius15 × D during installation
PackagingSteel drums, 250 – 600 m per drum
StandardIEC 60502-2, GB/T 12706.3

8.7/15 kV three-core copper, armoured — construction & ratings

Cross-sectionmm²Outer diameter≈mmApprox. weight≈kg/kmMax. DC resistance20 °CΩ/kmCurrent rating, in groundACurrent rating, in airA
3 × 35564,6000.524157173
3 × 50595,3000.387186207
3 × 70636,4000.268228257
3 × 95677,7000.193272313
3 × 120718,9000.153309360
3 × 1507410,2000.124346407
3 × 1857811,9000.0991391465
3 × 2408414,6000.0754453546
3 × 3008917,4000.0601510623

Standard reference values: current ratings for one circuit in trefoil, 90 °C conductor, 20 °C soil (1.5 K·m/W) or 30 °C air; dimensions and weights are typical. Final data depend on screen size and sheath — non-standard designs on request.

Inquire about this cable

Three-Core MV XLPE Armoured Cable 8.7/15 kV

Typical reply within one working day.

or sales@xinyapower.com