Three-Core MV XLPE Armoured Cable 8.7/15 kV
Three screened cores, one armoured cable — buried feeders without extra protection.
- Cross-section
- 3 × 35 – 3 × 300 mm²
- Rated voltage
- 3.6/6 – 18/30 kV
- Standard
- IEC 60502-2
Three-core medium-voltage cable to IEC 60502-2: each XLPE core individually screened with copper tape, laid up with fillers and protected by steel tape or steel wire armour under a PVC sheath. Laid directly in the ground for distribution feeders, industrial ring mains and transformer connections.
ModelsN2XSEYBY 3×95 8.7/15 kVYJV22 3×240 8.7/15 kVXY-MV3-SWA
- IEC 60502-2
- IEC 60228
- GB/T 12706.3
Highlights
- 3 × 35 – 3 × 300 mm², up to 18/30 kV
- Copper tape screen on every core
- STA or SWA armour for direct burial
- Copper or aluminium conductors
Technical data
| Model | N2XSEYBY 3×95 8.7/15 kV | YJV22 3×240 8.7/15 kV | XY-MV3-SWA |
|---|---|---|---|
| Rated voltage | 3.6/6, 6/10, 8.7/15, 12/20, 18/30 kV | ||
| Conductor | Compacted copper or aluminium, class 2 | ||
| Cross-section | 3 × 35 – 3 × 300 mm² | ||
| Construction | Three screened XLPE cores laid up with fillers, bedding, armour, outer sheath | ||
| Insulation | XLPE, triple extruded; 4.5 mm nominal at 8.7/15 kV | ||
| Metallic screen | Copper tape on each core | ||
| Armour | Double galvanised steel tape (STA) or galvanised steel wire (SWA) | ||
| Outer sheath | PVC (ST2), black; LSZH or HDPE on request | ||
| Operating temperature | 90 °C continuous conductor temperature | ||
| Short-circuit temperature | 250 °C, 5 s | ||
| Flame retardancy | Flame retardant, IEC 60332-1-2 | ||
| Min. bending radius | 15 × D during installation | ||
| Packaging | Steel drums, 250 – 600 m per drum | ||
| Standard | IEC 60502-2, GB/T 12706.3 | ||
8.7/15 kV three-core copper, armoured — construction & ratings
| Cross-sectionmm² | Outer diameter≈mm | Approx. weight≈kg/km | Max. DC resistance20 °CΩ/km | Current rating, in groundA | Current rating, in airA |
|---|---|---|---|---|---|
| 3 × 35 | 56 | 4,600 | 0.524 | 157 | 173 |
| 3 × 50 | 59 | 5,300 | 0.387 | 186 | 207 |
| 3 × 70 | 63 | 6,400 | 0.268 | 228 | 257 |
| 3 × 95 | 67 | 7,700 | 0.193 | 272 | 313 |
| 3 × 120 | 71 | 8,900 | 0.153 | 309 | 360 |
| 3 × 150 | 74 | 10,200 | 0.124 | 346 | 407 |
| 3 × 185 | 78 | 11,900 | 0.0991 | 391 | 465 |
| 3 × 240 | 84 | 14,600 | 0.0754 | 453 | 546 |
| 3 × 300 | 89 | 17,400 | 0.0601 | 510 | 623 |
Standard reference values: current ratings for one circuit in trefoil, 90 °C conductor, 20 °C soil (1.5 K·m/W) or 30 °C air; dimensions and weights are typical. Final data depend on screen size and sheath — non-standard designs on request.
Related products
Made in our plant
MV & HV power cablesSingle-Core MV XLPE Cable 6/10 – 26/35 kV (Cu / Al)
N2XSY 1×240/25 18/30 kV
- Cross-section
- 35 – 630 mm²
- Rated voltage
- 3.6/6 – 26/35 kV
- Standard
- IEC 60502-2
MV & HV power cablesHV XLPE Cable 64/110 kV, Corrugated Aluminium Sheath
2XS(FL)2Y 1×800 64/110 kV
- Cross-section
- 240 – 1,600 mm²
- Rated voltage
- 38/66 – 76/132 kV
- Standard
- IEC 60840
Made in our plant
LV power cables0.6/1 kV XLPE Copper Power Cable (CU/XLPE/PVC)
CU/XLPE/PVC 4×95
- Cross-section
- 1.5 – 630 mm²
- Rated voltage
- 0.6/1 kV
- Standard
- IEC 60502-1
Inquire about this cable
Three-Core MV XLPE Armoured Cable 8.7/15 kV
Typical reply within one working day.