HV XLPE Cable 64/110 kV, Corrugated Aluminium Sheath
High-voltage underground links for substations and city transmission.
- Cross-section
- 240 – 1,600 mm²
- Rated voltage
- 38/66 – 76/132 kV
- Standard
- IEC 60840
Single-core high-voltage cable to IEC 60840 with super-clean XLPE insulation, longitudinal water blocking, corrugated aluminium sheath and HDPE outer sheath with a conductive layer for sheath testing. Segmental Milliken conductors for large sections; lengths planned for each route section between joint bays.
Models2XS(FL)2Y 1×800 64/110 kVYJLW03 1×630 64/110 kVXY-HV110
- IEC 60840
- IEC 60228
- GB/T 11017
Highlights
- 38/66 – 76/132 kV, 240 – 1,600 mm²
- Corrugated Al sheath, radial watertight
- Milliken conductor above 1,000 mm²
- Route-length drums, joints on request
Technical data
| Model | 2XS(FL)2Y 1×800 64/110 kV | YJLW03 1×630 64/110 kV | XY-HV110 |
|---|---|---|---|
| Rated voltage | 38/66, 64/110, 76/132 kV (Um 72.5 – 145 kV) | ||
| Conductor | Compacted round copper up to 800 mm²; segmental (Milliken) copper 1,000 – 1,600 mm² | ||
| Cross-section | 1 × 240 – 1 × 1,600 mm² | ||
| Insulation | Super-clean XLPE, dry-cured, triple extruded on a VCV / CCV line | ||
| Water blocking | Semi-conductive water-swellable tapes (longitudinal) | ||
| Metallic screen | Corrugated aluminium sheath, or copper wire screen with Al-laminate tape | ||
| Outer sheath | HDPE with graphite or extruded semi-conductive layer for sheath testing | ||
| Operating temperature | 90 °C continuous conductor temperature | ||
| Short-circuit temperature | 250 °C, 5 s | ||
| Partial discharge | No detectable discharge at 1.5 U₀ (routine test) | ||
| Packaging | Steel drums, lengths per route section (typically 500 – 1,000 m) | ||
| Standard | IEC 60840, GB/T 11017 | ||
64/110 kV copper, corrugated aluminium sheath — construction & ratings
| Cross-sectionmm² | Insulation thicknessmm | Outer diameter≈mm | Approx. weight≈kg/km | Max. DC resistance20 °CΩ/km | Current rating, in groundA |
|---|---|---|---|---|---|
| 1 × 400 | 17 | 86 | 8,000 | 0.047 | 640 |
| 1 × 500 | 16 | 89 | 9,000 | 0.0366 | 720 |
| 1 × 630 | 16 | 93 | 10,400 | 0.0283 | 810 |
| 1 × 800 | 16 | 98 | 12,200 | 0.0221 | 900 |
| 1 × 1,000 | 16 | 103 | 14,400 | 0.0176 | 990 |
| 1 × 1,200 | 16 | 107 | 16,300 | 0.0151 | 1060 |
| 1 × 1,600 | 16 | 114 | 20,500 | 0.0113 | 1180 |
Standard reference values: current ratings for one circuit in trefoil, 90 °C conductor, 20 °C soil (1.5 K·m/W) or 30 °C air; dimensions and weights are typical. Final data depend on screen size and sheath — non-standard designs on request.
Related products
Made in our plant
MV & HV power cablesSingle-Core MV XLPE Cable 6/10 – 26/35 kV (Cu / Al)
N2XSY 1×240/25 18/30 kV
- Cross-section
- 35 – 630 mm²
- Rated voltage
- 3.6/6 – 26/35 kV
- Standard
- IEC 60502-2
Made in our plant
MV & HV power cablesThree-Core MV XLPE Armoured Cable 8.7/15 kV
N2XSEYBY 3×95 8.7/15 kV
- Cross-section
- 3 × 35 – 3 × 300 mm²
- Rated voltage
- 3.6/6 – 18/30 kV
- Standard
- IEC 60502-2
Made in our plant
LV power cables0.6/1 kV XLPE Copper Power Cable (CU/XLPE/PVC)
CU/XLPE/PVC 4×95
- Cross-section
- 1.5 – 630 mm²
- Rated voltage
- 0.6/1 kV
- Standard
- IEC 60502-1
Inquire about this cable
HV XLPE Cable 64/110 kV, Corrugated Aluminium Sheath
Typical reply within one working day.