MV & HV power cables

HV XLPE Cable 64/110 kV, Corrugated Aluminium Sheath

High-voltage underground links for substations and city transmission.

Cross-section
240 – 1,600 mm²
Rated voltage
38/66 – 76/132 kV
Standard
IEC 60840

Single-core high-voltage cable to IEC 60840 with super-clean XLPE insulation, longitudinal water blocking, corrugated aluminium sheath and HDPE outer sheath with a conductive layer for sheath testing. Segmental Milliken conductors for large sections; lengths planned for each route section between joint bays.

Models2XS(FL)2Y 1×800 64/110 kVYJLW03 1×630 64/110 kVXY-HV110

  • IEC 60840
  • IEC 60228
  • GB/T 11017

Highlights

  • 38/66 – 76/132 kV, 240 – 1,600 mm²
  • Corrugated Al sheath, radial watertight
  • Milliken conductor above 1,000 mm²
  • Route-length drums, joints on request

Technical data

Model2XS(FL)2Y 1×800 64/110 kVYJLW03 1×630 64/110 kVXY-HV110
Rated voltage38/66, 64/110, 76/132 kV (Um 72.5 – 145 kV)
ConductorCompacted round copper up to 800 mm²; segmental (Milliken) copper 1,000 – 1,600 mm²
Cross-section1 × 240 – 1 × 1,600 mm²
InsulationSuper-clean XLPE, dry-cured, triple extruded on a VCV / CCV line
Water blockingSemi-conductive water-swellable tapes (longitudinal)
Metallic screenCorrugated aluminium sheath, or copper wire screen with Al-laminate tape
Outer sheathHDPE with graphite or extruded semi-conductive layer for sheath testing
Operating temperature90 °C continuous conductor temperature
Short-circuit temperature250 °C, 5 s
Partial dischargeNo detectable discharge at 1.5 U₀ (routine test)
PackagingSteel drums, lengths per route section (typically 500 – 1,000 m)
StandardIEC 60840, GB/T 11017

64/110 kV copper, corrugated aluminium sheath — construction & ratings

Cross-sectionmm²Insulation thicknessmmOuter diameter≈mmApprox. weight≈kg/kmMax. DC resistance20 °CΩ/kmCurrent rating, in groundA
1 × 40017868,0000.047640
1 × 50016899,0000.0366720
1 × 630169310,4000.0283810
1 × 800169812,2000.0221900
1 × 1,0001610314,4000.0176990
1 × 1,2001610716,3000.01511060
1 × 1,6001611420,5000.01131180

Standard reference values: current ratings for one circuit in trefoil, 90 °C conductor, 20 °C soil (1.5 K·m/W) or 30 °C air; dimensions and weights are typical. Final data depend on screen size and sheath — non-standard designs on request.

Inquire about this cable

HV XLPE Cable 64/110 kV, Corrugated Aluminium Sheath

Typical reply within one working day.

or sales@xinyapower.com