Mga MV at HV power cable

Single-Core MV XLPE Cable 6/10 – 26/35 kV (Cu / Al)

Dumaraan sa triple extrusion sa sarili naming CCV line — pangunahing cable ng mga substation, wind farm at network sa lungsod.

Cross-section
35 – 630 mm²
Rated voltage
3.6/6 – 26/35 kV
Pamantayan
IEC 60502-2

Single-core medium-voltage cable ayon sa IEC 60502-2 na may compacted copper o aluminium conductor, conductor screen, XLPE insulation at insulation screen na ini-extrude sa iisang pasada, copper wire screen na angkop sa inyong fault level at PVC o PE sheath. Pumapasa ang bawat haba sa partial-discharge at AC voltage test bago lumabas ng pabrika.

Mga modeloN2XSY 1×240/25 18/30 kVNA2XS(F)2Y 1×400/35YJV 26/35 kV 1×50 – 1×630

  • IEC 60502-2
  • IEC 60228
  • IEC 60332-1-2
  • GB/T 12706.2

Pangunahing katangian

  • 3.6/6 hanggang 26/35 kV, 35 – 630 mm²
  • Triple extrusion, dry-cured sa CCV line
  • Copper wire screen na 16 – 35 mm² ayon sa fault level
  • May watertight at termite-proof na opsyon

Teknikal na datos

ModeloN2XSY 1×240/25 18/30 kVNA2XS(F)2Y 1×400/35YJV 26/35 kV 1×50 – 1×630
Rated voltage3.6/6, 6/10, 8.7/15, 12/20, 18/30, 26/35 kV
ConductorCompacted copper o aluminium, class 2 (IEC 60228); may longitudinal water blocking kapag hiniling
Cross-section1 × 35 – 1 × 630 mm² (800 mm² kapag hiniling)
KonstruksyonConductor screen, XLPE insulation at insulation screen na sabay na extruded (triple extrusion, CCV line)
InsulationXLPE, nominal na kapal na 8.0 mm sa 18/30 kV
Metallic screenCopper wire screen na may counter-helix copper tape, 16 – 35 mm² (ayon sa fault current)
Outer sheathPVC (ST2) o MDPE / HDPE (ST7); pula o itim
Operating temperature90 °C na temperatura ng conductor sa tuloy-tuloy na operasyon
Short-circuit temperature250 °C, 5 s
Flame retardancyFlame-retardant, IEC 60332-1-2
Partial discharge≤ 5 pC sa 1.73 U₀ (routine test sa bawat haba ng cable)
Minimum bending radius15 × D sa pag-install · 10 × D sa mga termination
PackagingSteel o wooden drums, 500 – 1,000 m bawat drum, may sealing caps sa mga dulo
PamantayanIEC 60502-2, GB/T 12706.2

18/30 kV single-core copper cable — konstruksyon at ampacity

Cross-sectionmm²Outer diameter≈mmTinatayang timbang≈kg/kmMaximum DC resistance20 °CΩ/kmAmpacity, nakabaon sa lupaAAmpacity, sa hanginA
1 × 50311,2500.387195235
1 × 70331,5000.268240290
1 × 95351,8000.193285350
1 × 120362,1000.153320400
1 × 150382,4000.124355450
1 × 185402,8000.0991400515
1 × 240433,5000.0754465610
1 × 300454,2000.0601520700
1 × 400495,2000.047590805
1 × 500526,4000.0366665920
1 × 630567,9000.02837451050

Mga standard reference value: ampacity para sa isang circuit na naka-trefoil, conductor na 90 °C, lupa na 20 °C (1.5 K·m/W) o hangin na 30 °C; karaniwang halaga ang mga sukat at timbang. Nakadepende ang pinal na datos sa laki ng screen at sheath — may custom design kapag hiniling.