Overhead conductors

Aerial Bundled Cable (ABC) 0.6/1 kV

Insulated LV overhead lines — safer, tidier and harder to tap illegally.

Cross-section
2 × 16 – 3 × 150 + 70
Rated voltage
0.6/1 kV
Standard
NF C 33-209

Twisted aerial bundled cable with XLPE-insulated aluminium phase cores around an insulated AAAC neutral messenger, to NF C 33-209 and BS 7870-5. Used for LV distribution through towns, villages and wooded areas, and for service connections.

ModelsNFC 33-209 3×70+54.6ABC 2×16JKLYJ / BS 7870-5

  • NF C 33-209
  • BS 7870-5
  • IEC 60502-1

Highlights

  • 2 × 16 to 3 × 150 + 70 mm²
  • UV-resistant black XLPE
  • Insulated AAAC neutral messenger
  • Ribbed core identification

Technical data

ModelNFC 33-209 3×70+54.6ABC 2×16JKLYJ / BS 7870-5
Rated voltage0.6/1 kV
ConductorCompacted aluminium phase cores, class 2
Neutral messengerInsulated AAAC neutral messenger (54.6 / 70 mm²)
InsulationBlack XLPE with carbon black, UV resistant
ConstructionPhase cores twisted around the neutral messenger; ribbed core identification
Operating temperature90 °C continuous conductor temperature
ApplicationLV distribution in towns and villages, service drops, areas with trees or theft risk
PackagingWooden or steel drums, 500 – 1,000 m
StandardNF C 33-209, BS 7870-5

Aerial bundled cable sizes (NF C 33-209)

SizePhase conductorNeutral messengerOuter diameter≈mmApprox. weight≈kg/kmCurrent ratingA
2 × 1616 mm² Al16 mm² Al1513583
4 × 1616 mm² Al16 mm² Al1827083
3 × 35 + 54.635 mm² Al54.6 mm² AAAC27590138
3 × 50 + 54.650 mm² Al54.6 mm² AAAC29720168
3 × 70 + 54.670 mm² Al54.6 mm² AAAC33880213
3 × 95 + 54.695 mm² Al54.6 mm² AAAC361,100258
3 × 150 + 70150 mm² Al70 mm² AAAC421,600344

Standard reference values from the conductor standards; other code sizes (ASTM, DIN, GB) on request.

Inquire about this cable

Aerial Bundled Cable (ABC) 0.6/1 kV

Typical reply within one working day.