How to size a 0.6/1 kV power cable: current rating and voltage drop

A worked example for a 75 kW motor feeder: design current, IEC 60364-5-52 current ratings, temperature correction and the voltage-drop check that usually decides the size.

By Xinya editorial team

How to size a 0.6/1 kV power cable: current rating and voltage drop

A low-voltage cable is correctly sized when it passes two checks: it can carry the load current without overheating, and the voltage at the far end stays within the allowed drop. Short-circuit withstand and protection coordination come on top, but these two decide most feeders.

1. Design current

For a three-phase load: I = P ÷ (√3 × U × cos φ). For a single-phase load: I = P ÷ (U × cos φ).

Example: a 75 kW motor at 400 V, cos φ 0.85 → I = 75,000 ÷ (1.732 × 400 × 0.85) ≈ 127 A.

2. Current-carrying capacity

IEC 60364-5-52 gives reference ratings for XLPE-insulated copper multicore cable (90 °C conductor). In free air or on a perforated tray (method E, 30 °C) a 35 mm² cable carries about 158 A, so it passes the current check.

Correct the rating for the real installation:

  • Ambient temperature: at 40 °C the factor for XLPE is about 0.91.
  • Grouping: several loaded circuits side by side on one tray reduce the rating further (IEC 60364-5-52 table B.52.17).
  • Installation method: the same 35 mm² cable carries about 144 A in conduit (method B2) and about 103 A in a buried duct (method D1, 20 °C soil).

3. Voltage drop

ΔU = √3 × I × L × (R cos φ + X sin φ), with R the conductor resistance at 90 °C (Ω/km), X ≈ 0.08 Ω/km for multicore cable and L in km.

For the same motor 150 m away:

  • 35 mm² (R ≈ 0.63 Ω/km): ΔU ≈ 19.1 V = 4.8 % — fails a 3 % limit
  • 50 mm² (R ≈ 0.44 Ω/km): ΔU ≈ 13.8 V = 3.4 % — still fails
  • 70 mm² (R ≈ 0.31 Ω/km): ΔU ≈ 10.2 V = 2.6 % — passes

So the feeder needs 4 × 70 mm², not 35 mm². On long runs voltage drop, not heating, decides the size.

4. Copper or aluminium?

From 16 mm² up, aluminium conductors (IEC 60228 class 2) are a valid alternative: about 1.6 × the copper cross-section for the same resistance, at a much lower cost per metre and weight. Use terminals and lugs made for aluminium.

5. Check the result

Our cable size calculator runs both checks for copper and aluminium, three installation methods and ambient temperature. Send us the result with your route lengths and we confirm the selection, including short-circuit rating and drum plan, within one working day.